Avaliação da Degradação Interna em Para-Raios de ZnO (192 kV) por Meio da Análise de Descargas Parciais e Padrões PRPD: Um Estudo de Caso
Keywords:
para-raios, descargas parciais, PRPD, degradação interna, manutenção preditivaAbstract
This paper presents a technical diagnosis of a 192 kV voltage-class lightning arrester using Partial Discharge (PD) analysis based on Phase-Resolved Partial Discharge (PRPD) diagrams. The objective was to correlate PD activity with the equipment's internal degradation state—considering electro-thermal aging effects and the oxidation of metallic and insulating components—across four experimental conditions organized into two physical configurations. In the first scenario, intense PD activity was observed, characterized by high-amplitude pulses and strong phase dependence, indicating severe internal defects associated with the structural degradation of zinc oxide (ZnO) blocks and metallic contacts. In the second scenario, a reduction in amplitude was noted, yet accompanied by a high repetition rate and a concentration of discharges in specific phase regions, consistent with discharges at degraded interfaces. Internal inspection revealed physical degradation consistent with the observed electrical patterns. The results indicate that integrated PD and PRPD analysis may offer a viable alternative for the diagnosis and predictive maintenance of high-voltage lightning arresters.Downloads
Published
2026-10-05
Issue
Section
Articles